Most failed sound insulation tests are not caused by the wall. They are caused by sound travelling around it. Here are the
Most failed sound insulation tests are not caused by the wall. They are caused by sound travelling around it. Here are the details that cause it, and what to check before the tester arrives.
In England and Wales, Approved Document E asks for airborne insulation of at least 43 dB DnT,w + Ctr for conversions and 45 dB for new build, with impact sound at or below 64 dB and 62 dB L’nT,w respectively. Higher is better for airborne; lower is better for impact.
You can build a separating wall that performs beautifully in a laboratory and still fail on site, because sound has found another path:
A specification is only as good as the build. The recurring site failures are sequencing errors: resilient layers bridged by fixings, acoustic mastic omitted at perimeters, plasterboard hard-fixed where it should be isolated, insulation left out of a floor void because it was easier to skip.
It is recoverable, and usually cheaper than people fear once the actual transmission path is identified rather than guessed at. Send the test report and the as-built construction, and the remedial work can be specified against what the results are telling you.
Note that pre-completion testing itself has to be carried out on site by an accredited testing body. We specify the design and tell you what testing your scheme needs; we do not carry out the tests.